Fzz heat exchanger analysis

Choose one exchanger segment or a chain of segments. Calculate outlet temperatures, heat duty and local heat transfer.

The stationary model covers counterflow and parallel flow with constant heat-capacity rates or prescribed isothermal boundaries. Choose Segmented HEX to simulate an inlet-temperature step with fluid residence times.

HEX configuration

Flow arrangement

Stream 1
Stream 2
Heat-transfer conductance

UA = 2,400 W/K

Formula selection and reference

Stationary results

Valid steady-state solutionExact Fzz relations
Heat transfer rate
207.515 kW
Stream 1 to stream 2
Stream 1 outlet
380.828 K
Stream 2 outlet
357.643 K
Total conductance UA
2,400 W/K

Temperature & heat transfer

Calculation formula in use

F2 · General counterflow

Exact relation selected.

Q˙=H(T1,in−T2,in)

H = 1,383.43331 W/K

Paired T–Q trajectories

The coordinate follows stream 1. Stream 2 flows from right to left. Points mark segment boundaries. Stream 1 is solid and stream 2 is dashed.0103.8207.5285375465Cumulative |Q̇| (kW)Temperature T (K)
Stream 1 (solid)Stream 2 (dashed)
Colours identify the streams in either direction of heat transfer. Stream 2 flows from right to left. The horizontal axis shows the cumulative magnitude of heat transfer.

Local results and verification

Local temperatures and heat transfer
SegmentUA (W/K)T₁,in (K)T₁,out (K)T₂,in (K)T₂,out (K)Q̇ (kW)Ṡgen (W/K)
12,400450380.828300357.643207.515132.014
Balances and whole-network accuracy

Boundary energy residual is 2.037e-10 W. The normalized residual is 9.817e-16.

The exact single-contact reference at the same total UA gives 207.514997 kW. The relative network duty deviation is 0%, computed against that reference for this constant-capacity chain.

Formula selected for each segment
SegmentProposedAppliedH (W/K)Weight sCandidate H error (%)Applied H error (%)
1F2F21,383.433313—00

Segment 1 · Exact relation selected.

Entropy & exergy

Entropy generation
132.01403 W/K
Exergy destruction
39.35998 kW

Fzz formulas, selector and transitions

Exact relations and limiting cases

G = UA; H = Fzz; Q̇ = H(T₁,in − T₂,in). For positive finite capacities:

F2 · x = G(1/C₁ − 1/C₂)
H = (1 − exp(−x)) / (1/C₁ − exp(−x)/C₂)

F3 · H = GC/(G + C), exact in counterflow when C₁ = C₂ = C.

F5 · H = [1 − exp(−G(1/C₁ + 1/C₂))] / (1/C₁ + 1/C₂)

F1 · H = C₁[1 − exp(−G/C₁)]
F4 · H = C₂[1 − exp(−G/C₂)]

F1 is exact for an isothermal stream 2 boundary; F4 for an isothermal stream 1 boundary. For finite capacities they are reservoir approximations. Two prescribed isotherms give H = G. F0 gives zero duty at zero capacity, but stationary outlet temperatures are undefined; this calculator requires positive finite flowing capacities.

At equal capacities the continuous F3 limit is used. G = 0 gives zero heat transfer. Exponential evaluations use expm1 and nonpositive-exponent branches for numerical robustness.

All selector regions and six transition formulas

Define ρ = max(C₁,C₂)/min(C₁,C₂). The equal-capacity approximation uses C = Cₑq = 2/(1/C₁ + 1/C₂).

RegionC₁ < C₂C₁ > C₂
Counterflow · 1 ≤ ρ ≤ 1.005F3 (exact at C₁ = C₂)
Counterflow · 1.005 < ρ < 1.01F32 = (1 − s)F3 + sF2F23 = (1 − s)F3 + sF2
Counterflow · 1.01 ≤ ρ ≤ 5F2
Parallel flow · 1 ≤ ρ ≤ 5F5
Counterflow · 5 < ρ < 10F12 = (1 − s)F2 + sF1F24 = (1 − s)F2 + sF4
Parallel flow · 5 < ρ < 10F15 = (1 − s)F5 + sF1F54 = (1 − s)F5 + sF4
Both arrangements · ρ ≥ 10F1F4

s = 6t⁵ − 15t⁴ + 10t³, clamped to [0, 1]. Near equal capacities, t = (ρ − 1.005)/0.005. Towards reservoir limits, t = (ρ − 5)/5. Symbols F1–F5 in these sums denote the corresponding H values.

A proposed formula is applied only when its relative H deviation from F2 (counterflow) or F5 (parallel flow) is within the selected tolerance and its physical bound is satisfied. Otherwise the exact relation is applied. The acceptance boundary can introduce a small jump even though the candidate transition is smooth.

F0 · Zero flow; stationary outlets undefined

F1 · Stream 2 reservoir limit

F2 · General counterflow

F3 · Equal-capacity counterflow

F4 · Stream 1 reservoir limit

F5 · General parallel flow

F12 · F2 to F1 transition

F24 · F2 to F4 transition

F23 · F3 to F2 transition; C₁ > C₂

F32 · F3 to F2 transition; C₁ < C₂

F15 · F5 to F1 transition

F54 · F5 to F4 transition

Coupling, entropy balance and inverse calculations

Stream 1 connects segment j to j + 1. Stream 2 connects j to j − 1 in counterflow, or j to j + 1 in parallel flow. The two outlet equations per segment are solved together as a linear system. Isothermal boundaries retain their prescribed temperatures.

For each flowing stream, ΔṠ = C ln(Tout/Tin). For an isothermal boundary, ΔṠ = Q̇received/T. Summing both contributions gives Ṡgen. Exergy destruction is T₀Ṡgen.

The inverse local route computes G = |Q̇|/ΔTlm from positive terminal differences. This is exact for the stated paired linear-in-duty interval; temperature-dependent trajectories require sufficiently fine intervals and refinement checks. A zero or crossed driving temperature difference is rejected.

Local selector error concerns H only. The shared model also reports the network duty deviation against the exact same-total-UA reference. It does not infer a complete cycle efficiency, COP or reversible-cycle benchmark from HEX results alone.

How this model is used in the Academy

Model assumptions and links to cycle calculations

This calculator and the Carnot external-stream contacts use the same Fzz core. Brayton external-stream conductance and the T–A mapping use its inverse local conductance relation on successive paired trajectory intervals. Their N₂ enthalpy and entropy properties remain temperature dependent; the entire Brayton trajectory is not replaced by a constant-cₚ exchanger.

For constant capacities and exact local formulas, the segmented chain reproduces the single-contact boundary result at the same total UA. Local temperatures and heat duties can differ. The displayed network deviation compares the selected chain against that exact reference; a local selector tolerance is not a guaranteed whole-network error bound.

The time simulation adds fluid storage and transport delays to the local Fzz contacts. It applies to two flowing streams with fixed properties and conductance. Wall storage, pressure loss and phase change require additional equations. Subdividing this chain keeps the stream properties constant.

Thermal Matching articleCycle external heat exchangeTerms & symbols