HEX performance analysis
Enter the heat-exchanger conditions once. Compare exergy destruction, reversible reference work and heat-recovery targets from the same stream data.
Start with the 100 kW counterflow example or transfer an operating point from Fzz.
Exchanger trajectories
Both diagrams describe the same exchanger. The heat and area coordinates start at the cold inlet. The area calculation uses dQ̇ = U ΔT dA at the U entered below.
T–Q · Actual exchanger
- Hot stream
- Cold stream
T–A · Actual exchanger
- Hot stream
- Cold stream
How to read the results
Actual operating point and exergy destruction
The calculation assumes an externally adiabatic exchanger with positive absolute temperatures and two constant-capacity streams. It models the thermal contribution to entropy generation. An assessment including pressure losses, heat leaks, mixing or auxiliaries needs the corresponding full balances.
The hot and cold streams exchange positive entropy magnitudes. The equations use rates for steady operation or totals per reference cycle, according to the selected basis.
The entropy generation equals the difference between these magnitudes. Equivalently, integrate the local entropy generation along the paired heat-transfer trajectory.
At the chosen reference-environment temperature, exergy destruction gives the lost work.
For a heating service entirely at or above , the exergy efficiency is the cold stream’s exergy gain divided by the hot stream’s exergy consumption.
Reversible references and what each one holds fixed
The three references below retain both inlet temperatures and stream capacities. With two reversible thermal contacts, the Clausius equality determines one free outlet. The energy balance then gives the reference work.
- Fixed source cooling. Keep the hot outlet and solve for the cold outlet.
- Fixed heat delivery. Keep the cold outlet and solve for the hot outlet.
- Fixed stream states and ambient contact. Keep both outlets and add reversible heat input from the reference environment.
With equal source and delivered duties, . This gives the lost work of the actual zero-shaft-work case.
The two-contact references pair equal increments of entropy transfer. They require a nonnegative local temperature difference for heat-engine operation. Each reference describes a reversible limit under its stated constraints.
Pinch targets and the area diagram
Pinch Analysis shifts the hot and cold temperatures by half the chosen minimum approach. It then cascades net heat across the shifted intervals. The utility targets and maximum heat recovery apply to steady sensible streams with constant capacities and unrestricted matching.
The T–A diagram uses the actual exchanger’s stream pairing and a constant overall heat-transfer coefficient .
For these linear temperature trajectories at positive duty and finite , the calculated area grows without bound as a terminal temperature difference approaches zero. Sizing individual exchangers from a composite curve requires a defined network and local stream matches.
See Linnhoff and Hindmarsh, The pinch design method for heat exchanger networks.
Relation to the CarnotX reversibility studies
The two companion studies show how an idealised non-isothermal Brayton cycle can move between zero net work and a reversible endpoint by changing hot-side matching, cold-side matching or internal component performance. Both heat duties determine net work. Holding both fixed also fixes net work, even if the temperature trajectories change.
The performance tool applies this distinction to an exchanger with fixed stream capacities and explicit service constraints. The Reversible Cycle Benchmark also has separate exploratory routes that vary only temperatures or heat quantities.
Sources and model scope
The lost-work examples draw on technical reports and research documents prepared by the CarnotX research team.
For the distinction between reference-environment exergy destruction and work loss under other system constraints, see Tu and Chen, Rethinking Loss of Available Work and Gouy–Stodola Theorem.